1. The floor-plan doesn't appear to match the health departments description of bedroom/bathrooms being served by the size septic system listed on their permit.

Please provide the Florida Environment Health Departments approved floor plans which match what is being constructed. 

ADDED ON 02/12/2021; Hold inspection 105 for approved floor plan from Health per H.T.

 

2. Please submit the Florida Energy Form designed to the new FBC-R 2020 code.

2/12/2021 jdacosta

3. Please provide the approved testing agency report for the Spray Foam Insulation being used.

2/12/2021 jdacosta

4. Please submit the type roof covering and the corresponding product approval numbers for it.

2/12/2021 jdacosta
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
2/12/2021 jdacosta