| | Department Issues | Signed Off | Intl |
|
|
1. STRUCTURES SEAWARD OF THE COASTAL CONSTRUCTION CONTRROL LINE (CCCL): Rear porch deck revision seaward of CCCL requires DEP (Florida Department of Environmental Protection) Approval. The package from DEP should contain dimensioned site plan, dimensioned cross-section, (exterior lighting plan stamped with SJ-number) and notice to proceed with scope of work.
|
7/30/2018
| dking |
|
|
2. STRUCTURES (Decks & Porches) SEAWARD OF THE COASTAL CONSTRUCTION CONTROL LINE (CCCL): Please provide construction details complying with ASCE 24-05 (sections 4.5 & 9.5) and R322.3 of the Florida Residential Building Code. They should be sited to remain in the ground during design flood conditions (i.e. on piles) or be designed and constructed to break away during flood conditions without producing debris capable of causing significant damage to any structure.
|
7/2/2018
| dking |
|
|
3. Please submit a complete truss package, identified by EOR as meeting his design or provide letter verifying truss package has been reviewed by EOR (Engineer of Record). (FBC-R802.10.1). (FL Rule 61G15-31.003) (Roof not part of this permit 6/29/18)
|
7/2/2018
| dking |
|
|
4. Please Provide Elevation Drawings: Please provide required Elevation Drawings missing for rear porch/deck addition. Provide two complete and accurate architectural plans (FBC-R107.3.5)
|
7/2/2018
| dking |
|
|
5. ENGINEERING DETAIL NEEDED: Please provide framing/attachment requirements for new porch roof tie-in to existing house.
|
7/2/2018
| dking |