| | Department Issues | Signed Off | Intl |
|
|
1. It appears the master bedroom does not comply with R310.1 FBCR
---Please provide Emergency Escape opening for the master bedroom
-----------SEE ITEM 2 BELOW
|
| |
|
|
2. Please provide the ICC_ES report for the spray foam insulation being used.
|
11/1/2021
| janoda |
|
|
3. V Zone Certificate Required from Engineer Of Record http://www.sjcfl.us/BuildingServices/media/forms/VZoneCertificate.pdf
|
11/1/2021
| janoda |
|
|
4. Pile Report Required before permitting http://www.sjcfl.us/BuildingServices/media/forms/AffidavitAcknowledgerequirementforpileinstalltion.pdf
|
| |
|
|
5. An Approved Site Plan and Floor Required from Health Dept.
-----------SEE ITEM 5 BELOW
|
| |
|
|
1. Job Copy submission has 2 pages of the North & East Elevation and is missing South & West Elevations
One of the North and East Elevations does not represent the changes
|
| |
|
|
2. Office copies submitted do not represent the changes and match job copies
Please remove and replace all required pages to correlate plan sets
|
| |
|
|
3. Septic tank is not addressed in the plans for having piles installed.
Please address septic tank piles
|
| |
|
|
4. Energy sheets are missing manual D pages
---Please submit 2 copies of missing documents
|
| |
|
|
5. Please provide a site plan approved by the health department.
|
| |