| | Department Issues | Signed Off | Intl |
|
|
1)All architectural pages refer to the asce 7-02 and 120 mph wind speed please change this to reflect the current standard asce 7-10 and 130 mph zone
|
6/19/2017
| blaw |
|
|
2)Page A 3 has a dimension line indicating 35'6" keeping in mind max height is 35' from lowest adjacent grade please explain this dimension line.
|
6/19/2017
| blaw |
|
|
3)FYI --The future pool will require additional permitting and dep approval as part of it lays seaward of the cccl
|
5/19/2017
| blaw |
|
|
4)Please provide a v zone design certificate.
|
6/19/2017
| blaw |
|
|
5)Please provide a pile report affidavit.
|
6/19/2017
| blaw |
|
|
6)FYI--a concrete tile roof permit will be required.
|
5/19/2017
| blaw |
|
|
7)FYI--A flat roof permit will be required.
|
5/19/2017
| blaw |
|
|
8)Please provide a 29" clear opening throughout the full bath down stairs (including the water closet room) as per R-320 of the 2014 FBC Residential.
|
6/19/2017
| blaw |
|
|
9)FYI-- The future bath, bedroom, closet etc. will require additional permitting at time of completion of this area.
|
5/19/2017
| blaw |
|
|
10)Please provide a current es report on the open cell spray foam to be used. Please circle the use of an ignition barrier on this es report.
|
6/19/2017
| blaw |
|
|
11)Please indicate that the garage door opener receptacles are to be gfci protected as per E 3902.2 of the 2014 FBC-Residential.
|
6/19/2017
| blaw |
|
|
12)Please disclose where the propane is coming from and illustrate the location on the site plan. Section 7.4.1 of the ASCE 24-05 addresses tanks that service a building and section 3.03.10 flood resistant development of the St. Johns County Land Development Code also addresses this.
|
6/19/2017
| blaw |
|
|
13)Please review the decimal point # for the concrete roof tiles for accuracy under the 2014 FBC selection.
|
6/19/2017
| blaw |
|
|
14)Please provide details on the copper roof at the dormer on the west elevation.
|
6/19/2017
| blaw |
|
|
15)Please provide the product approval # for the velux sun tunnel.
|
6/19/2017
| blaw |
|
|
16)Please provide product approval #/engineering on the copper dormer vents illustrated on the east and west elevations.
|
6/19/2017
| blaw |
|
|
17)Please provide product approval #'s on the flat roof material.
|
6/19/2017
| blaw |
|
|
18)Please identify what type of soffit material is to be used and provide a product approval # as appropriate.
|
6/19/2017
| blaw |