Clearance Sheet R2017-000656

 Department IssuesSigned OffIntl

1)All architectural pages refer to the asce 7-02 and 120 mph wind speed please change this to reflect the current standard asce 7-10 and 130 mph zone

6/19/2017 blaw

2)Page A 3 has a dimension line indicating 35'6" keeping in mind max height is 35' from lowest adjacent grade please explain this dimension line.

6/19/2017 blaw

3)FYI --The future pool will require additional permitting and dep approval as part of it lays seaward of the cccl

5/19/2017 blaw

4)Please provide a v zone design certificate.

6/19/2017 blaw

5)Please provide a pile report affidavit.

6/19/2017 blaw

6)FYI--a concrete tile roof permit will be required.

5/19/2017 blaw

7)FYI--A flat roof permit will be required.

5/19/2017 blaw

8)Please provide a 29" clear opening throughout the full bath down stairs (including the water closet room) as per R-320 of the 2014 FBC Residential.

6/19/2017 blaw

9)FYI-- The future bath, bedroom, closet etc. will require additional permitting at time of completion of this area.

5/19/2017 blaw

10)Please provide a current es report on the open cell spray foam to be used. Please circle the use of an ignition barrier on this es report.

6/19/2017 blaw

11)Please indicate that the garage door opener receptacles are to be gfci protected as per E 3902.2 of the 2014 FBC-Residential.

6/19/2017 blaw

12)Please disclose where the propane is coming from and illustrate the location on the site plan. Section 7.4.1 of the ASCE 24-05 addresses tanks that service a building and section 3.03.10 flood resistant development of the St. Johns County Land Development Code also addresses this.

6/19/2017 blaw

13)Please review the decimal point # for the concrete roof tiles for accuracy under the 2014 FBC selection.

6/19/2017 blaw

14)Please provide details on the copper roof at the dormer on the west elevation.

6/19/2017 blaw

15)Please provide the product approval # for the velux sun tunnel.

6/19/2017 blaw

16)Please provide product approval #/engineering on the copper dormer vents illustrated on the east and west elevations.

6/19/2017 blaw

17)Please provide product approval #'s on the flat roof material.

6/19/2017 blaw

18)Please identify what type of soffit material is to be used and provide a product approval # as appropriate.

6/19/2017 blaw