1. Please submit approved St Johns County Product Approval Sheet with specific products that will be used with current 2014  FL#.

 

2. Please describe the bifold door utilized in the carport (as it will be exposed to humidity).

 

3. Please address interior footer supporting wall and trusses A06-A09 footer appears to change direction and supporting wall will no longer bear on footer.

 

4. Please indicate wall thickness, the carport walls and columns scale at 12" with nothing indicating otherwise .

 

5. Please indicate top cord dead load on print to support roof type.

 

6. Please draw site plan to "FBC 107.2.5 Site Plan" scale and size (dimensions).

 

7. Please address Energy sheet not matching print: insulation R-value, wall type in garage, roof coverage as there are several discrepancies between the plans and the energy sheet.

 

8. Please provide "Prepared by" Signature and the "Owner Agent" Signature on the energy sheet.

 