PLEASE PROVIDE A POOL LAYOUT DRAWING: Provide a representative dimensioned layout drawing of the pool & spa and relationship to the house, including depth of the pool. (FBC-R107.2.1 & 107.2.5)

4/5/2021 dking

MISSING TDH Flow Rates and Calculation Sheet (Per ANSI/APSP 5 & 7): Please provide, TDH Calculations for maximum pump speed including components to be installed. (per FBC-R 4501.6.1)

4/5/2021 dking

Plans Not Clear or Missing Information:  
- Please provide clear and legible filter equipment manufacturers product sheets with make and model to be installed clearly identified. Please provide two complete and accurate sets of plans (FBC-R107.3)

FILTER SHEET WASN'T LEGIBLE.

4/5/2021 dking