SJC Home
Clearance Sheet R2015-003315

 Department IssuesSigned OffIntl

1. The Code Analysis indicates "Partially Enclosed" internal pressures (-.55+.55) whereas the truss engineering is enclosed. Please correlate.

 

2. Submit the current Florida Energy Form (form 405-14) also please provide individual forms for each structure.

 

3. Please identify all habitable spaces of the Guest House.  

 

4. Please identify all interior bearing footers with the required reinforcing steel.

 

5. Please identify all exterior and interior headers also identify all supporting king and jack studs.

 

6. The on/center spacing of all-thread rods are listed at 4 foot on center. Please identify the uplift at doors and windows wider than foot.

 

7. Please submit dormer framing detail with all uplift connections shown.

 

8. The E.O.R. is required to review, approve, sign and date the delegated roof truss engineering.

 

9. Please provide a detail of roof and window flashing at Bedroom #4 3050 window located below roof line.

 

10. Please refer to FBC-R 2014 Table 1001.1 for chimney clearances. The chimney doesn't appear to meet the 2 foot by 10 foot rule.

 

11. Please identify the post/column supports under each multi-ply girder.

 

12. Please identify all shear-wall sections and the required uplift connections and each end of each section.

 

13. Please provide a ledger detail for all porch conventional roof and ceiling rafter connections to the house.  

 

14. Please provide the multi-ply beam fastening schedule.

 

15. Please submit the ICC ES Report for the spray foam insulation being used.

 

16. Please identify Guest House porch rafter connection to main structure.

 
17. An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.  
18. General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
 
19. Pen and ink changes, white-outs, or any such altering of raised seal engineering drawings, is not permitted under state laws governing the practice of Architecture or Engineering. All information on the raised seal drawings must part of the printed sheets at the time the drawings are sealed by the Architect/Engineer.