SJC Home
Clearance Sheet R2014-001910*002

 Department IssuesSigned OffIntl

SIGNED & SEALED: All drawings prepared by an Florida Registered Design Professional (Architect or Engineer) shall be signed and sealed. FBC 2017 107.1

Pages S1-S7 are missing the engineers seal

8/18/2021 dking

Missing Truss package :.
Please submit a complete truss package, identified by EOR (engineer of record) as meeting his design or provide letter verifying truss package has been reviewed by EOR (Engineer of Record). (FBC-R802.10.1).
(FL Rule 61G15-31.003) (R502.11)

8/18/2021 dking

Missing Energy Sheets:   

The Florida Energy Conservation Code (FECC), Section R101.5.1.1 provides two options for compliance with building thermal envelope requirements. Please indicate if you will be using the "Prescriptive option (building thermal envelope alternative Form R402)" or the "Simulated performance method". If using the Form 402 Prescriptive option please provide two completed copies acknowledging that the listed code requirements will be done. Or provide Energy Sheets using the simulated performance method.

Contact me if you need copies of the Prescriptive Forms (904-827-6814)

8/18/2021 dking

Florida Product Approval: (As required by Florida Statute 553.842 and Florida Administrative Code 9B72)
Please provide/revise/provide Florida Product Approval Sheets to show product approval numbers for Simpsons Strong-tie anchors and hold downs referenced. Specific products are identified by the decimal places.  Missing sheet & numbers for roofing, siding & soffits. Typically the installation instructions are for inspection purposes and the product approval for is for permanent record.

8/18/2021 dking