SJC Home
Clearance Sheet R2014-001515*004

 Department IssuesSigned OffIntl

1. The structure is located seaward of the Coastal Construction Control Line (CCCL) and requires a Dept. of Environmental Protection (DEP) permit.

---Please provide a DEP permit for the proposed construction.

 

2. The Florida Building Code Residential Section R322.1.11 requires structures seaward of the CCCL to comply with Section R322 of the FBC Residential and Section 3109 of the FBC Building. More specifically but not limited to R322.3 Foundations and R322.3.8 Decks.

--- Please provide foundation specifications (pile foundation) complying with the FBCR-R322 and FBCB 3109 for all foundation related work performed seaward of the CCCL.

 

3. The proposed expansion for the bedroom and the closet over the garage does not appear to identify the load path from the roof to the foundation.

---Please provide details identify the load path supporting the new expansion. 

 

4. The proposed expansion for the bedroom and the closet over the garage does not appear to identify the floor system.

---Please provide details for the floor system and how it will be supported.