| | Department Issues | Signed Off | Intl |
|
|
1. BUILDER IS NOT THE OWNER: Per Florida Statutes 489 The building or residence must be for my own use or occupancy. It may not be built or improved for sale or lease.
|
| |
|
|
2. Design Criteria (FBC-R301.2.1.1): Please list the design criteria used for those portions of the structure not covered by the concrete construction elements designed in accordance with this code and our basic wind speed, (the wood framed portions of the structure designed per one of the approved methods i.e., ASCE 7-10, ICC-600, WFCM for One-and two-Family Dwellings, …) .
|
| |
|
|
3. ENGINEERING FOR THIS PROJECT APPEARS TO BE MISSING STRUCTURAL ELEMENTS: Please review supporting structure and load path requirements for this structure (FBC-R107). There appears to be missing beams, headers, interior bearing supports, structural posts, opening framing requirements, interior spot footings and possibly more. Review stopped due to missing information.
|
| |
|
|
4. METAL ROOFING : Please verify roof sheathing required for the type roofing being used and properly reference on the appropriate plan sheets, (Note: your plans reference 7/16" roof sheathing and the roofing may require a different product, such as 15/32").
|
| |
|
|
5. ENERGY SHEETS: Please submit Energy Sheets as required per FECC (Florida Energy Conservation Code) 101.4.3 for additions, alteration, renovations or repairs. Per Table 101.4.1 the addition & renovation must meet current Energy Code.
|
| |
|
|
PLANS General Notes: Your re-submittal should include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, should be marked as "old set" and should be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON NEW INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
AS PER ORDINANCE # 98-42 An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.
|
| |