Define design criteria method per Section R301.2.1.1 2010 FBC Residential for regions where the ultimate design wind speed is in excess of 115mph.

9/11/2013 dgriffin

Readdress wind borne debris protection due to the change in definitive line for 2010 Building Code, to include Note #8 under structural notes.

9/11/2013 dgriffin

Provide details in regards to seperation of garage from residence  per Section R302.5 & R302.6, and Table 302.6 of the FBC-Residential.

9/11/2013 dgriffin

Provide stair detail per sizing requirements and referances to Section R302.7 FBC-R 2010.

9/11/2013 dgriffin

Clarify descrepancy between vinyl windows on energy forms and aluminum windows on product approval list.

9/11/2013 dgriffin