| | Department Issues | Signed Off | Intl |
|
|
1. Site plan (both copies) is not legible. Please submit new, legible site plans clearly showing all details, including setback dimensions and Lot Coverage.
Note: Maximum Lot Coverage, stated on Clearance Sheet, is 40%. Lot Coverage calculated on plans is 47%. Please clarify. New site plans must be signed off by Zoning.
Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and show in detail that it will conform to the provisions of this code and laws, ordinances, rules, and regulations.
|
11/21/2013
| darlington |
|
|
2. Please submit Energy Sheets, including Manual J, and Manual D or equivilant.
|
11/21/2013
| darlington |
|
|
3. Spray Foam Insulation. Please specify the spray foam insulation to be used and submit the ES Report for that product. ES Reports have optional applications. Please indicate all options on the ES report, including ignition and thermal barriers. Interior living and attic storage spaces require a thermal barrier over all foam plastic materials, including spray foam, ICF, and SIPS panels.
|
11/21/2013
| darlington |
|
|
4. Please review FBC-R314, NFPA 72, and R315 and note correct locations of Smoke and Carbon Monoxide Detectors on plans.
|
11/21/2013
| darlington |
|
|
5. Please clarify ground level of this project, including bearing and uplift on existing structure, roof drainage off ridge, and flashing.
|
11/21/2013
| darlington |
|
|
6. Second-story windows do not appear to meet emergency escape openings, FBC-R310 or window sill height, FBC-R612.2. Many 2'-8" x 5'-0" SH windows do not open to 5.7 sf. Please review Code Sections, provide window documentation, and clarify windows.
|
11/21/2013
| darlington |
|
|
7. Florida Product Approval. This location is in Wind Exposure 'D'. Some products that usually qualify in Exposure 'B' will not qualify in this location; that is the case with several products on this project. For examples, please find the JOB COPY Sheets and see red marks. Please revise Florida Product Approval Sheets to show all products indicated and decimal places of Numbers. Product Approval Numbers usually include more than one product. Specific products are identified by the decimal places.
Please verify all products meet design pressures on Page S-0.0.
|
11/21/2013
| darlington |
|
|
8. This site is in the FEMA AO Flood Zone and must comply with all FEMA requirements.
|
11/21/2013
| darlington |
|
|
General Notes: Your re-submittal should include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, should be marked as "old set" and should be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON NEW INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
11/21/2013
| darlington |