SJC Home
Clearance Sheet R2011-000006

 Department IssuesSigned OffIntl

1. Please specify and detail exterior wall covering over gable-end truss.  Decorative Cementitious Coating does not qualify, per FRC, Chapter 7

2/4/2011 jdacosta

2. Please provide details for bond beam and rebar location lintels.
   Please verify garage door lintel.

2/4/2011 jdacosta

3. Please review FBC-R609.3 and vertical rebar at openings on plans.  Provide details for openings.

ADDED ON 02/04/11; Item not fully addressed. Please submit details clarifying lintel descriptions; 8F8-0B, 8F8-1B, 8F16-1B, PS8-8, PS8-12, PS8-20. Also submit the Florida Product Approval numbers for both.

 

4. Please submit porch ceiling materials and details. Building is designed as Enclosed. Verify angled hanger for porch beam.

ADDED ON 02/04/11; Please submit the ES Report and/or the Florida Product Approval number for the product listed.

 

5. Please identify all sheathing fasteners and provide a fastening schedule.

2/4/2011 jdacosta

6. Please submit the masonry to truss connector schedule which meets the uplift values provided by the truss engineer.

ADDED ON 02/04/11; Connectors provided appear to be wood to truss connectors. Please submit the masonry to truss connector schedule.

 

7. This project is located in the Wind-Borne Debris Region. As such, plans must include provisions for protection of openings per 2007 FBC-Building Section R301.2.1.2 w/2009 supplements.

2/4/2011 jdacosta

8. NOT A COMPLETE LIST.
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.