1. Please provide letter from truss manufacturer for the additional concentrated live load applied to the system 42 pre-engineered floor trusses.

 

2. The minimum uniformly distributed live load for exterior balconies is 60 pounds per square foot, your design is 40 pounds per square foot.

 

3. Please provide microlam installation instruction with span tables, minimum bearing requirements and multiple member connection details.

 

4. Please provide detail of Guardrail attachment to roof member. The note for "Handrail" does not meet the FBC-R for a minimum 36 inch guardrail height. Please revise note for Guardrail's.