Please provide letter from truss manufacturer for the additional concentrated live load applied to the system 42 pre-engineered floor trusses.
|
1/14/2011
| ccrain |
|
|
The minimum uniformly distributed live load for exterior balconies is 60 pounds per square foot, your design is 40 pounds per square foot.
|
1/14/2011
| ccrain |
|
|
Please provide microlam installation instruction with span tables, minimum bearing requirements and multiple member connection details.
|
1/14/2011
| ccrain |