SJC Home
Clearance Sheet R2010-000594

 Department IssuesSigned OffIntl
Effective July 1, 2008 St. Johns County will be required to enforce the installation of Carbon Monoxide Detectors in all new construction as per Rule No. 9B-3.0472, Florida Administrative Rule. Please identify on plans the locations of all Carbon Monoxide Detectors installed according to code listed above. 6/25/2010 ccrain
Specify on plans the required anchors for ground-mounted mechanical equipment per one of the methods in FBC-R, section M1307.3.1. 6/25/2010 ccrain
1. Window sill height: a new section, R613.2, in the 2007 FBC requires a minimum window sill height of 24 inches above the finished floor. There are several design options that comply with the new provisions, some of them may effect emergency escape and rescue openings and appearance of the building. Please review Section FBC-R613.2,engineered header sizes, ASTM F2006, and ASTM C2090 and indicate on plans how the second story windows meet the new requirement. 6/25/2010 ccrain
Specify/Detail on plans, the stucco application, incorporating the bond-breaker required by FBC-R, section 703.6 6/25/2010 ccrain
The Engineer of Record is required to review and approve the work of the delegated truss design engineer prior to submittal for permitting. Provide truss engineering showing approval of the EOR. 6/25/2010 ccrain
This project is located in the Wind-Borne Debris Region. As such, plans must include provisions for protection of openings per 2007 FBC-Building Section R301.2.1.2 w/2009 supplements. 6/25/2010 ccrain

DEP permit # and address must match plan # and address.

6/25/2010 ccrain

EPL card missing from Energy Sheets.

6/25/2010 ccrain

Need certification by manufacture that air handler enclosure qualifies as certified factory sealed.

6/25/2010 ccrain

Final inspection will be held for Florida Class 1 Rater reports on system test and envelope leakage. 

6/25/2010 ccrain

Complete Product Approval Form to match plans.

6/25/2010 ccrain

Need manufactures installation instructions for Liquid Applied Roof System. Minimum slope is 2%.

6/25/2010 ccrain

Provide detail and roof drain calculations for balcony roof and  parapet areas with scuppers.

6/25/2010 ccrain

Plans call for detail 6/S-4, please provide.

6/25/2010 ccrain

Specify height of parapets that are functioning as guards around balcony area.

6/25/2010 ccrain

Please provide detail for exterior wall covering at column and break-away wall sections.

6/25/2010 ccrain

Locate smoke detectors on plans at all require locations.

6/25/2010 ccrain

Please provide correct detail on plans the separation requirements from the garage to habitable space above.

6/25/2010 ccrain

The area below the 100 year storm elevation may be used only for storage, access and parking. The area below the 100 year storm elevation shall not contain mechanical, electrical or plumbing devices.The space is limited to the minimum lighting, switching, receptacle and smoke detector requirements. Please adjust the plan to reflect.

6/25/2010 ccrain

Please complete and sign the Non Conversion Agreement for structures seaward of the CCCL. 

6/25/2010 ccrain
Please provide a proposal from the engineer of record or a approved testing agency for the onsite installation inspection of each piling. The proposal must include the followings: Total Number of Installed Piles, Total Length of Installed Piles, Piles installed in accordance with drawings and specifications, Exceptions to pile placements (as built), Description of installation equipment and procedure for installation, Blow count, and Site conditions. 6/25/2010 ccrain