| | Department Issues | Signed Off | Intl |
|
|
1. Please provide updated plans for construction to include the minimum requirements on attached sheet.(sheet is the jp2007 attachment to plans)
ADDED ON 04/28/10; Please see specific comments below
|
5/7/2010
| jdacosta |
|
|
2. Please submit product approval for slider winder in bedroom #3.
|
5/7/2010
| jdacosta |
|
|
3. The Florida Energy Efficiency calculations indicate the HVAC AHU's to be electric whereas sheet #5 indicates gas furnace. Please review and correlate plans.
|
5/7/2010
| jdacosta |
|
|
4. Please sign/date the Energy Performance Level display card located in the Ecalc's. Also complete checklist.
|
5/7/2010
| jdacosta |
|
|
5. Please submit manufacturers specification for corner sliding glass door unit indicating which glass thickness is being used to meet the end zone design pressures.
|
5/7/2010
| jdacosta |
|
|
6. Carbon Monoxide alarms are required within 10' of each bedroom. Please add Carbon Monoxide alarms to the floor plan per R313.4
|
5/7/2010
| jdacosta |