| | Department Issues | Signed Off | Intl |
|
|
1. Please provide updated product approval for exterior doors and french door in sales area.
|
| |
|
|
2. The submitted site plan is missing dimensions from the exterior walls to the property line. Please add the dimensions missing dimensions to the site plan.
|
| |
|
|
3. The project is located in the wind borne debris zone and requires opening protection. Please indicate on the plans what method of opening protection will be incorporated and provide product approval if applicable.
|
| |
|
|
4. Please modify the typical masonry wall detail to comply with the stucco requirements of R703.6
|
| |
|
|
5. The engineer of record references 1609.1.2 for opening protection. Please revise reference to the 2007 Florida Building Code Residential Section R301.2.1.2.
|
| |
|
|
6. Please have the truss engineer provide a fastening schedule for the truss hangers.
|
| |
|
|
7. Please provide a elevation drawing and framing detail for the sales office.
|
| |
|
|
8. Please indicate on the plans were the carbon monoxide sensors will be located.
|
| |
|
|
9. Please provide a masonry wall uplift schedule.
|
| |
|
|
10. Please provide a readable interior bearing wall detail.
|
| |