The submitted DEP permit specified that the SPGP Authorization was not granted. Please show additional documentation of their authorization.

Resubmittal- See scanned images clearance sheet

1/6/2009 RCW

Zoning requires that the plans need to have ARC approval. Please provide this approval in writing.

1/6/2009 RCW

The block wall portion of the retaining wall shows spade anchors for tie backs. Please provide additional documentation specifing model number, installation specifics and connection info at the block wall.

1/6/2009 RCW

Please depict on the engineering (regarding the wooden bulhead)fasteners for:

1. Stringers to the piles
2. Tie Backs to the piles and to the deadmen
3. Heavy duty vinyl sheet (Cribbing) to the stringers

1/6/2009 RCW