Please provide a larger readable scale sheet A106.D101, D102, and D103. The plans must be readable in the poor lighting conditions inside the house under construction.
|
4/24/2008
| JNP |
|
|
Please provide a Quicktie detail and indicate the location of each Quicktie on the floor plan.
|
4/24/2008
| JNP |
|
|
Please revise the specification for the roof nailing to "ring shank"
|
4/24/2008
| JNP |
|
|
Please provide a fastening schedule opening protection panels.
|
4/24/2008
| JNP |
|
|
Please provide the location for the overturn connections.
|
4/24/2008
| JNP |
|
|
Please provide a continous uplift connection from truss R1A to the foundation.
|
4/24/2008
| JNP |