Please provide a larger readable scale sheet A106.D101, D102, and D103. The plans must be readable in the poor lighting conditions inside the house under construction.

4/24/2008 JNP

Please provide a Quicktie detail and indicate the location of each Quicktie on the floor plan.

4/24/2008 JNP

Please revise the specification for the roof nailing to "ring shank"

4/24/2008 JNP

Please provide a fastening schedule opening protection panels.

4/24/2008 JNP

Please provide the location for the overturn connections.

4/24/2008 JNP

Please provide a continous uplift connection from truss R1A to the foundation.

4/24/2008 JNP