The building is located in a FEMA AH flood zone with a minimum elevation of 7 feet. Since this project is a substantial improvement then you will be required to meet 7 NGVD. Please provide a elevation certificate showing a minimum finished floor of 7 NGVD.
Not a complete review.
Please provide a wall framing plan regarding the rear french doors area. Specify headers, kings, jacks, and uplift connectors. Note what design criteria was used in the wall design( Include basic wind speed, wind exposure and importance factor).
Please provide the Florida Product Approval Number for the roofing wood shingle. You may have to contact the manufacturers regional distributor to obtain it.