The plans submitted shall be engineered under the provisions of the 2007 Florida Building Code with 2009 Supplements.  Additional items may be required depending on information and clarity of final plans submitted.

4/1/2010 ccrain

All drawings prepared by an Florida Registered Architect or Engineer shall be signed and sealed. FBC 2007 106.1

4/1/2010 ccrain

Effective July 1, 2008 St. Johns County will be required to enforce the installation of Carbon Monoxide Detectors in all new construction as per Rule No. 9B-3.0472, Florida Administrative Rule. Please identify on plans the locations of all Carbon Monoxide Detectors installed according to code listed above.

4/1/2010 ccrain

Specify on plans the ductwork in garage; comply with FBC-R, section R309.1.1, OR specify 1-hr rated fire dampers at wall and/or ceiling penetrations, OR enclose equipment and ducts in separate closet with door as required by FBC-R309.1. No duct openings into garage are permitted under any of these options.

4/1/2010 ccrain

Specify on plans the materials and means for separation of garage from habitable space; comply with FBC-R, section R309.2.

4/1/2010 ccrain

Specify materials and attachment of structural closure required for wind-load pressures at ceilings of open porches on this Enclosed Structure. Reference section R703.1.1. 

4/1/2010 ccrain

Specify on plans the required anchors for ground-mounted mechanical equipment per one of the methods in FBC-R, section M1307.3

4/1/2010 ccrain

Specify/Detail on plans, the stucco application, incorporating the bond-breaker required by FBC-R, section 703.2.1. unless vinyl is the only wall covering? Missing sheet A1.0 detail 4.  

4/1/2010 ccrain

Window flashing detail needed on plans.

4/1/2010 ccrain

Please provide a structural floor framing plan showing length of shear walls and stud to sole plate connections.

4/1/2010 ccrain

Please provide Florida product approval numbers for wood connectors.

4/1/2010 ccrain

Please provide site specific engineering for screen wall at rear of house or remove notes from the plan.

4/1/2010 ccrain