Clearance Sheet R2006-002483*003

 Department IssuesSigned OffIntl

1. Architectural drawing does not refer to the correct code cycle.

---Please have the Architectural drawing code cycle reference changed to represent the current 2020 cycle including the ASCE 7-16.

---Please note that a licensed Architect should seal their drawings per Chapter 481 of the Florida Statutes

4/8/2021 janoda

2. R322.3.3 Foundations.

Buildings and structures erected in coastal high-hazard areas and Coastal A Zones shall be supported on pilings or columns and shall be adequately anchored to such pilings or columns.

--- It appears there are no structural details for the pergola including piles, attachments, fasteners etc...

---If the pergola is not going to be constructed at this time please mark it as not part of this permit including the site plan. 

4/15/2021 janoda

3. A V Zone Building Design Performance Certificate is required to be completed by the designer of record for review prior to permitting.

---Please provide a V zone certificate for review

4/15/2021 janoda

4. Please provide the ICC_ES Report for the sprat foam insulation.

---The test data report should be provided by the supplier for the product being used.

4/15/2021 janoda