MISSING ENGINEERED TRUSS PLANS: Truss plans submitted are not signed/sealed by engineer and missing design criteria (per FBC-R502.11).

NOTE: The girder trusses labeled 'B & F' appear to be switched on plans. The triple floor truss appears to be in the wrong location.

 

Please provide a column detail for the support on the triple floor truss girder (FBC-R107 & 107.3.5).

 

Please review outstanding comments from original permitting. They still need to be addressed.

 

Outstanding Comments Not Addressed by Revision Submitted:

1. Please provide the anticipated finished floor elevation in the NGVD datum to demonstrate compliance with the current design flood elevation. (Originally on page 8.0 of plans)

2. DETAIL/MISSING WALL SECTION DETAIL:

- Please provide a complete 2-story wall section detail showing materials, including interior wall covering, insulation material, and exterior wall finish with details, (FBC-107).  Plans have several conflicting details. Please have all documents correlate, (roofing pitch & type, attic insulation, wall insulation, floor truss bearings, truss to bond beam connection, vertical rebar spacing, ......)

 

3. Please provide a complete foundation page showing all footers interior and exterior. (FBC-R107).

Note: Detail E/2.0 footing depth is the same as the required anchor bolt penetration detail A/3.0

 SHEET 2.0 (FBC-R107)

- Please clarify when on the lintel table is an A or B type designation used for the specific locations .

- Missing plans for spiral stairs and surrounding floor system framing details.

- Provide PSL bearing requirements/support for bedroom 3 wall bearing point.

 

Please provide roof sheathing and attachment matching metal roofing requirement of 15/32" on the Florida Product Approval sheet.