1. Provide 1/4" scale floor plan of proposed remodeling of the existing garage/workshop. Show location of proposed Pella sliding glass door. Show locations of all existing or new walls, windows and doors, with sizes of windows and doors.
|
6/28/2006
| TEW |
|
|
2. The proposed door from garage directly to the bedroom is not permitted. See '04 Florida Building Code - Residential (FBCR) section R309.1.
|
6/28/2006
| TEW |
|
|
3. If a door is to be installed from garage to any habitable space other than the bedroom, plans must specify the type and thickness of the door per FBC-R309.1.
|
6/28/2006
| TEW |
|
|
4. Provide the Florida Product Approval number for the proposed sliding glass door (or any other proposed new windows or doors).
|
6/28/2006
| TEW |
|
|
5. Energy Efficiency forms indicate the exterior walls are "Concrete". Provide a detail showing how the proposed R-13 wall insulation will be accomplished.
|
6/28/2006
| TEW |
|
|
6. Provide insulation at ceiling of conditioned space; submit corrected energy efficiency forms.
|
6/28/2006
| TEW |
|
|
7. Specify on plans the separation of garage from habitable space as required by FBC-R309.2.
|
6/28/2006
| TEW |
|
|
FYI: A minimum 4" clearance is required at all sides of mechanical equipment and components (FBC-R, section M1601.3.3).
|
6/28/2006
| TEW |
|
|
FYI: Ground-mounted mechanical units shall be anchored per FBC-R, section M1307.3.1.
|
6/28/2006
| TEW |
|
|
FYI - REVIEW OF PLANS SUSPENDED. ADDITIONAL ITEMS MAY BE REQUIRED, DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|