| | Department Issues | Signed Off | Intl |
|
|
1. Please submit a certified Elevation Certificate.
|
1/3/2014
| jdacosta |
|
|
2. Windows appear to not match from the floor plan to the elevations. Please correlate.
|
1/3/2014
| jdacosta |
|
|
3. The "Partial West Elevation" missing second floor window.
|
1/3/2014
| jdacosta |
|
|
4. The new second floor bedroom indicates 2 3044 windows. It appears this size window will not meet the code (5.7 sq. ft.) for Means of Excape. Please review and revise.
|
1/3/2014
| jdacosta |
|
|
5. The floor trusses and floor beams are missing. Please submit trusses approved by the E.O.R.
|
1/3/2014
| jdacosta |
|
|
Pen and ink changes, white-outs, or any such altering of raised seal engineering drawings, is not permitted under state laws governing the practice of Architecture or Engineering. All information on the raised seal drawings must part of the printed sheets at the time the drawings are sealed by the Architect/Engineer.
|
1/3/2014
| jdacosta |
|
|
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
1/3/2014
| jdacosta |
|
|
AS PER ORDINANCE # 98-42 An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.
|
1/3/2014
| jdacosta |