| | Department Issues | Signed Off | Intl |
|
|
Please submit ES Evaluation Report for the spray foam insulation indicated on plans. Specify on the report which method is to be used.
|
8/26/2011
| dgriffin |
|
|
There is a conflict of information, on sheet S-2 6X6 post is indicated. Then on sheet S-3 4X4 post is referred to for the porch columns.
|
8/26/2011
| dgriffin |
|
|
There is no specific reference to the header for the sliding glass doors from the sitting room to the porch other than a general statement that all headers are to be 2x6. Is this the case for such a significant header.
|
8/26/2011
| dgriffin |
|
|
Please provide some assisting detail for the vaulted ceiling in the sitting room in regards to the ceiling joist configuration.
|
8/26/2011
| dgriffin |