| | Department Issues | Signed Off | Intl |
|
|
R320.1.1 Accessibility - Please provide bathroom with a 29" clear opening.
|
| |
|
|
Truss package shows A02 14 pieces. Truss diagram shows A02 with 5 pieces. Please provide corrected Truss package sheet.
|
| |
|
|
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
| |
|
|
Please provide 2 copies of the ICC/ES Sprayfoam Report.
|
| |