1.  Corrections from 04/07/06 were not addressed.  Review 04/07/06 Issues Report and address all issues.
    Some additional issues follow.  Plan Review was suspended - too many issues.

$100.00 Additional Plan Review Fee was added.

 
FYI - PLANS NOT REVIEWED. ADDITIONAL ITEMS MAY BE REQUIRED, DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.  
FYI-AS PER ORDINANCE # 98-42 “ An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.This is your second re-submission.  

4.  Truss drawings do not match architectural drawings regarding roof pitch and height of trusses.
    Building height must be less than 35'.  Height of floor and roof trusses, as per Truss Drawings,
    results in building height over 35'.
    
    New truss drawings must be signed-off by EOR.

    Provide Truss Layouts at readable size and scale.
   

 

5.  Provide complete engineering, including beam specifcations and profile sheets, lintel schedule,
    Wind Design Data, opening protection, etc.

 

7.  Provide all Product Approval information on one type of document, including roofing material over
    Covered Patio.

 

8.  This is not a complete list.  Plan Review suspended.