SJC Home
Clearance Sheet R2006-000242

 Department IssuesSigned OffIntl
1. Clearance Sheet requirements include: 1. Site is seaward of the CCCL. 2. Special conditions of CCCL Permit must be met. 3. DEP Permit required. 4. Maximum building height is 35 feet, this plan indicates 42 feet. Please submit plans that conform to the Clearance Sheet requirements or contact Developement Services to modify Clearance Sheet. PLANS WERE NOT COMPLETELY REVIEWED. DUE TO THE ABOVE ISSUES AND THE POTENTIAL REVISIONS THEY MAY CAUSE, PLANS WERE ONLY PARTIALLY REVIEWED.  
2. Review "Wall types" on Energy Sheets for insulation. R-11 (Energy Sheet) vs. R4.1 (Plans).  
Specify on plans the required anchors for ground-mounted mechanical equipment per one of the methods in FBC-R, section M1307.3.1.  
Printed plans submitted for review on or after December 5, 2005, must include the following information required by the 2004 Florida Building Code - Residential: specify metal ducts in garage (R309.1.1), or see the Nov. 1 notice for alternatives to metal ducts approved for use in this county; specify thickness and material of door from garage to living space, or specify 20 minute fire-rated door (see R309.1); specify separation of garage from habitable space (R309.2); specify min. clearances around mechanical equipment (M1601.3.3); specify anchoring of outside mechanical units (M1307.3.1); detail the flashing requirements for windows per bulletin published by BOAF, First Coast Chapter, Codes and Standards Committee. For stucco on wood frame exterior walls specify and detail the stucco application including "bond-break" as required by R703.2.1. A copy of the notice dated November 1, 2005, is attached for your edification.  
Specify on plans the clearances required at mechanical equipment; comply with FBC-R, section M1601.3.3.  
Specify on plans the materials and means for separation of garage from habitable space; comply with FBC-R, section R309.2.  
Specify on plans the ductwork in garage; comply with FBC-R, section R309.1.1, OR specify 1-hr rated fire dampers at wall and/or ceiling penetrations, OR enclose equipment and ducts in separate closet with door as required by FBC-R309.1. No duct openings into garage are permitted under any of these options.  
Specify on plans the door material and thickness of door from garage to habitable space; comply with FBC-R, section R309.1.  
4.  
Please clarify continuous uplift, frame construction, and shear walls at raised towers over garages. (E/S-7), including F78-80.  
Specify/Detail on plans, the stucco application, incorporating the bond-breaker required by FBC-R, section 703.2.1.  
Provide details on plans for flashing wall openings per BOAF First Coast Chapter Codes and Standards Committee Bulletin.  
Specify (8) beams shown on floor truss layout.  
FYI - PLANS NOT REVIEWED. ADDITIONAL ITEMS MAY BE REQUIRED, DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW. See Item #1.  
NOTE: For cantilever porch support, please review 2004FBC Table 1904.2.2(1) or corrosion protection for structural steel in a salt environment.