Does this glass room affect emergency egress from a bedroom as per FBC R310?
11/26/07 Contractor called said there is no issue.
|
11/26/2007
| RCW |
|
|
The site is located in an exposure C but the foundation and structure were designed as an exposure B. Please make any necessary changes to the plans such as the design criteria and possibly the structural components.
|
11/29/2007
| RCW |
|
|
The energy form has specified this structure is not to be heated or cooled. You will be required to fill out a no heat/cool affidavit available in the building dept. I believe it must be signed by the owner and notarized.
|
11/29/2007
| RCW |
|
|
The horizontal slider with the Florida Product Approval Number 3512.1 has a design pressure of + or - 15 psf. This does not comply the 2004 FBC-R Table R301.2(2).Please specify a window that will meet this requirement.
|
11/29/2007
| RCW |