Does this glass room affect emergency egress from a bedroom as per FBC R310?

11/26/07 Contractor called said there is no issue.

11/26/2007 RCW

The site is located in an exposure C but the foundation and structure were designed as an exposure B. Please make any necessary changes to the plans such as the design criteria and possibly the structural components.

11/29/2007 RCW

The energy form has specified this structure is not to be heated or cooled. 
You will be required to fill out a no heat/cool affidavit available in the building dept.

I believe it must be signed by the owner and notarized.
11/29/2007 RCW

The horizontal slider with the Florida Product Approval Number 3512.1 has a design pressure of + or - 15 psf. This does not comply the 2004 FBC-R Table R301.2(2).Please specify a window that will meet this requirement.