AS PER ORDINANCE # 98-42 “An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.
|
| |
|
|
1. Architect of record needs to sign and seal his/her drawing per State Statute 481.221(1)(a).
|
| |
|
|
2. Missing the size of windows and doors.
|
| |
|
|
3. Missing roof covering material from plans.
|
| |
|
|
4. Every sleeping room located on the first, second and third story shall have at least one emergency escape and rescue opening per section1005.4 of the FBC
|
| |
|
|
5. Smoke detector is required in close proximity to the stairway leading to the floor above per 905.2.2 of the FBC. Smoke detector are required in close proximity to door leading into the bedroom per 905.2.2 of the FBC show on plans. Smoke detector are required in bedroom per 905.2.1 of the FBC show on plans.
|
| |
|
|
6. The connector for truss T02 at joint 7 doesn't provide the required uplift per truss engineering.
|
| |
|
|
7. The connector for truss T10 at joint 6 doesn't provide the required uplift per truss engineering.
|
| |