Clearance Sheet R2005-005086

 Department IssuesSigned OffIntl
1 – Area calculations was not included with resubmit, please furnish. 2 – Window design pressures as listed within the submitted Product Approvals do not meet the stated pressures given by the Engineer of Record (-36psf). Please re-specify and resubmit. The product approval submittals must be in congruence with the plans. 3 – This project is located in an Exposure C zone and is within a Wind Bourne Debris area. Therefore, the openings must be provided with protection or furnish impact glass within the windows and glass doors. Please specify and resubmit.