The job copy plan has a typical wall section crossed out. Please supply a new sheet.
|
11/8/2006
| RCW |
|
|
Please specify the design criteria as required by the 2004 FBC-R301.2.1.1. (Example: SSTD 10-99 or AF&PA WFCM)
|
11/8/2006
| RCW |
|
|
Please specify on the plan that the design complies with the 2004 Florida Building Code –Residential
|
11/8/2006
| RCW |
|
|
Stucco over felt back wire lath is required to have a bond break consisting of one layer of an approved water resistant barrier over an approved plastic house wrap as specified by 2004 FBC 1404.2.1.
Your plan does not specify this plastic house wrap. Please specify this on your plan.
|
11/8/2006
| RCW |
|
|
The truss package does not include the jack J-02, J-03, and J-04. Please include these.
|
11/8/2006