Zoning requires a 35' maximum height measured from the peak of the roof to the lowest adjacent grade. Please revise and resubmit. Unable to review plans until this issue is resolved. 5/19/2005 JNP
Provide one-hour rated assemblies for floor/ceiling, roof/ceiling, exterior walls, interior bearing walls, columns, and beams to comply with FBC 709 or listed assemblies. 5/19/2005 JNP
Provide one-hour listed assembly detail sheets for electrical, plumbing, and mechanical penetration passing into or through rated floor/ceilings, roof/ceilings, exterior walls, and interior bearing walls. 5/19/2005 JNP
Indicate on the floorplan were the HVAC fire dampers will be located. Fire dampers are required were duct pass into or through a rated assembly. 5/19/2005 JNP