1. At least one copy of all engineering submittals must have raised seal from Engineer of Record (EOR), including span tables.  
Specify all dimensions, framing member sizes, and center/center spacing for all structural members on signed/sealed site-specific drawings.  
Please review spans for all roof and wall framing members and provide calculations.  
Review wall and roof bracing. Indicate the means by which the structure will resist lateral loads, including twisting and racking loads and provide calculations. Show all roof, wall, and cable bracing on site-specific drawings.  
Provide calculations for beam to beam connections. Address moment connection, size and location of gusset plates (with no splice at flanges),and screw pattern.  
FYI-ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW