Per FBC 1007.4.2, a landing is required at bottom of interior stair between bottom riser and doorway.
Suggest you consider deleting the subject door and wall segment(s) to resolve this issue.
A doorway could be added at 2nd floor hallway if desired for privacy purposes.
|
| |
|
|
Reference detail 6/S-1B, 3 Simpson A35 connectors stacked end-to-end will not fit the 11 1/4" beam depth.
It further appears that the capacity of all 6 connectors will be exceeded by the imposed load.
Provide calculations and corrected connection detail as appropriate.
|
| |
|
|
It appears that the proposed Microlam ridge beam over Gathering Room will deflect approximately
1.6", thereby exceeding the recommended deflection for roof structure. Provide calculations and
corrected documents as appropriate.
|
| |
|
|
As a "heads-up", plans have been marked to show that handrails are required at exterior
steps if the number of risers is 4 or more. Reference FBC 1007.5.
No response required on this issue.
|
| |