SJC Home
Clearance Sheet R2004-002740*007

 Department IssuesSigned OffIntl

1. Master suite and Suite #3 appear to emergency escape onto a screened porch with a hard roof. Please refer to code section below regarding, open to the atmosphere. One solution is to remove the screen from in front of these areas, remove references to screen from the drawings.

R310.1Emergency escape and rescue opening required.

Basements, habitable attics and every sleeping room shall have not less than one operable emergency escape and rescue opening. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room. Emergency escape and rescue openings shall open directly into a public way, or to a yard or court that opens to a public way.

Exceptions:

  1. 1.Storm shelters and basements used only to house mechanical equipment not exceeding a total floor area of 200 square feet (18.58 m2).

  2. 2.The emergency escape and rescue opening shall be permitted to open into a screen enclosure, open to the atmosphere, where a screen door is provided leading away from the residence.

3/4/2022 jdacosta

2. The Exterior wall detail references spray foam insulation whereas the Florida Energy Forms indicate Vented Attic. Please correlate.

If Spray foam insulation is to used please include the I.C.C. E.S. Report or equivalent testing report for the spray foam insulation being used. 

3/4/2022 jdacosta
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
3/4/2022 jdacosta
Pen and ink changes, white-outs, or any such altering of raised seal engineering drawings, is not permitted under state laws governing the practice of Architecture or Engineering. All information on the raised seal drawings must part of the printed sheets at the time the drawings are sealed by the Architect/Engineer. 3/4/2022 jdacosta