| | Department Issues | Signed Off | Intl |
|
|
Your resubmittal should include three sets of plans or you may insert
the revised pages into the plan sets and one set of the original shall
be resubmitted.
ALL ITEMS REVISED SHALL BE IDENTIFIED.
ADDITIONAL ITEMS MAYBE REQUIRED - DEPENDING ON INFORMATION AND CLARITY
OF FINAL PLANS SUBMITTED FOR REVIEW
AS PER ORDINANCE # 98-42 "An additional fee due and payable at permitting
shall be of $100 each for any second resubmission of plans." Per FL.
Statute 553.80(2)(b), on any third and subsequent resubmissions that
do not correct a code violation that is specifically and continuously
noted in each previous rejection, a fee of four times the amount of the
fee attributed to plan review will be charged.
All changes to the plans shall be identified by “clouding”, nomenclature
and other readily identifiable means.
|
6/30/2004
| WJD |
|
|
1. Structure has been designed for partially-enclosed, therefore
Tables used for C & C out of FBC cannot be used since that is for B Exposure.
Please correct.
|
6/30/2004
| WJD |
|
|
2. Indicate which tables are applicable through highlighting or some other means,
See sheets A-11 and A-12.
|
6/30/2004
| WJD |
|
|
3. Indicate fastenings for Double Sheathing (DSW). Uplift connectors, manufacturer’s
name and item number with the size and number of nails. Note: This is required for
the wall sections, shear wall connectors, roof connectors and moment overturn
connectors, i.e., all connectors required to be installed.
|
6/30/2004
| WJD |
|
|
4. The requirements for conventional roof framing, provide the rafter/joist
layout drawing showing the size, spacing of members and the structural ridge
and full bearing to foundation. The manufacture’s name, connector item number
and nail/fastener requirements. Bracing shown on conventional framing indicates trussing.
Submit Calculations. Spans appear too great for tables provided. FBC 2301 & 2309
|
6/30/2004
| WJD |
|
|
5. Submit uplift schedule for all conventional framing.
|
6/30/2004
| WJD |
|
|
6 .The location of the smoke detectors shall be shown on the plans.
|
6/30/2004
| WJD |