GENERAL NOTES: Your resubmittal should include three sets of plans or you may insert the revised pages into the plan sets and one set of the original shall be resubmitted. ALL ITEMS REVISED SHALL BE IDENTIFIED. ADDITIONAL ITEMS MAYBE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW AS PER ORDINANCE # 98-42 "An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans." Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged. All changes to the plans shall be identified by “clouding”, nomenclature and other readily identifiable means. 4/16/2004 WJD
1. Submit calculations for shearwalls, appears to be to small of quanity. 4/16/2004 WJD
2. Truss connector for B1 is not adequate to handle uplift. 4/16/2004 WJD
3. No scabs shown on truss plans for H1 yet structural plans call for scab, please verify. Please verify connectors for truss H1. 4/16/2004 WJD
4. Truss data sheets for O8- 010 Trusses are missing. 4/16/2004 WJD