| | Department Issues | Signed Off | Intl |
|
|
1. A9-c requires the net area of openings; 8inch x 16inch x 8 openings equals 1024 sq.in. The note in Section D for Smart Vents satisfies the requirement for 1600 sq.in.
|
| |
|
|
2. FEMA requires for documentation a copy of the ES Report for the engineered smart vents.
|
| |
|
|
3. It appears the lowest piece of equipment (A/C) to be to low.
|
| |