| | Department Issues | Signed Off | Intl |
|
|
1. It appears the CWS 4040 Horizontal Slider Window doesn't meet the 5.7 sq ft minimum means of escape for 2nd story windows. Unable to verify the Product Approval number given for CWS Horizontal Slider Windows. Please refer to the CWS Window Size Chart provided and chose a window size marked with an asterisk that meets the code for means of escape.
|
6/24/2015
| jdacosta |
|
|
2. Please provide the Florida Product Approval number for the Sliding Glass Doors being used.
|
6/24/2015
| jdacosta |
|
|
3. The drawings appear to show Asphalt Shingle roof cover whereas the Florida Energy Form indicates Metal. Please correlate.
|
6/24/2015
| jdacosta |
|
|
4. Please verify if a post is required at frame-wall end of 3 ply F-05.
|
6/24/2015
| jdacosta |
|
|
5. AS PER ORDINANCE # 98-42 An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.
|
6/24/2015
| jdacosta |
|
|
6. General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
6/24/2015
| jdacosta |
|
|
7. Pen and ink changes, white-outs, or any such altering of raised seal engineering drawings, is not permitted under state laws governing the practice of Architecture or Engineering. All information on the raised seal drawings must part of the printed sheets at the time the drawings are sealed by the Architect/Engineer.
|
6/24/2015
| jdacosta |