Clearance Sheet R2003-001952*001

 Department IssuesSigned OffIntl

Received revised plans.

Please provide a roof framing layout for the conventionally framed roof.

Tuesday, January 08, 2008 Received revised A-3. The roof framing layout for the Master Bedroom shows "Pre- Engineered Wood Trusses" and notes for a conventionally framed roof. If you are using trusses, please provide. If the roof will be conventionally framed, the ceiling joist are undersized. Please clarify and revise.

1/10/2008 JNP

Please provide over framing detail for area is not covered by trusses at Playroom.

1/8/2008 JNP

The Playroom shows a relocated window, please provide product approval showing a minimum -38PSF and opening protection.

1/8/2008 JNP

Add smoke detectors to the inside of Master bedroom and in the hall outside of the Master bedroom.

1/8/2008 JNP