Clearance Sheet R2003-001271

 Department IssuesSigned OffIntl
Job Name:Homestead Estate lot8 Job address: 205 Shirley's Way Plan Reviewer: M. Reid Flood zone: C Contr.Name:Robshwm James Phone # 904-471-1120 Lic. # Arch.Name: Phone # Lic. # Eng.Name:Lawrence Paine Phone # Lin. # 21475 Occp Type: R3 Const. Type: VI Spkl. : No Occp. Load: Your resubmittal should include three sets of plans or you may insert the revised pages into the plan sets and one set of the original shall be resubmitted. ALL ITEMS REVISED SHALL BE IDENTIFIED. ADDITIONAL ITEMS MAYBE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW AS PER ORDINANCE # 98-42 “ An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2) (b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.  
Show location of smoke detectors on the plan per section 905.2 of the FBC.  
Missing connectors for trusses T02 & T09 truss due to uplift.  
Hughes connector is no longer available. Specify connectors that available.  
Missing spacing of the porch post.  
Provide eggress window for second floor bedroom.  
Floor plan show a elevation of 20' the clearance sheet as floor elevation of 25'.  
Missing connector from header to jack studs for typical header for doors and windows  
Provide spacing and information for alternate 1/2" all thread.  
Provide mechanical ventilation for second floor bathroom rooms per table 403.3 of the FMC.  
Provide stair details showing rise and run, handrails height and spacing of intermediate rail per sections 1007 & 1015.3of the FBC.  
Provide framing plan for wood deck showing lumber used, connectors ect.  
Clarify is a fireplace is going to be installed. Elevation show a chimney but floor plan doesn't have fireplace location.