Plans show right facing garage, the siteplan shows a left facing garage. Please revise plans to match siteplan. 6/5/2003 JNP
Bedroom three window does not appear to meet the requirements for emergency egress. When the window is open, it must have a minimum clear opening of 24" high and 20" wide and a clear opening of 5.7 square feet. 6/5/2003 JNP
Arch window detail needs additional reinforcement at the round top radius. 6/5/2003 JNP
Indicate location of shearwalls and overturn connections. 6/5/2003 JNP
Provide truss layout for a left facing garage. 6/5/2003 JNP
Floor truss layout shows an overall dimension of 22' 4" at the rear of the future bonus room. Second story shows 18' 2". Please revise. 6/5/2003 JNP
Provide a continous uplift connection from B3, D3, and A5 to the foundation. 6/5/2003 JNP