2. The Designer of Record will be required to include the Lanai/Sunroom construction on these construction documents and assume responsibility for that construction.
The supporting post (removed from the corner of the Lanai) has shifted the bearing of the roof to the sunroom framed walls which are supported on a thickened edge open porch footer.
The cantilevered porch beams not only are carrying the original roof they are also carrying the additional "addition" roof load.
All framing, connections details (of the unpermitted addition) will need to be included on these drawings.