Received a revision to change the ceiling joist and beams supporting the ridge support post and the ceiling joist. Please refer to table R301.5 and provide calculation to confirm that the 2x10 beams specified are adequate to support the ridge support post and the ceiling joist. Please specify joist hangers and include a fastening schedule.

3/15/2010 JPAULA

Please provide a second copy of the sheets S-2 and S-3.

3/15/2010 JPAULA