| | Department Issues | Signed Off | Intl |
|
|
Please submit health department review permit containing an approved floor plan and site plan for septic system.
|
| |
|
|
Architectural drawing page A.8 drywall ceilings do not meet code R302.6
|
6/13/2024
| mhamilton |
|
|
Please review and resubmit product approvals for windows and doors to indicate the specific Florida product approval number used so that it may be verified as impact resistant.
|
| |
|
|
Top Chord Dead Load indicated on structural design criteria is 20psf but is noted as 10psf on the truss engineering sheets. Top Chord Dead Load on S0.1 does not match top chord dead load on submitted truss package.
|
| |
|
|
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
|
| |