The minimum height for nonalarmed doors accessing a pool is 54". The submitted plan shows 64".
|
6/2/2006
| GVB |
|
|
The minimum load bearing foundation wall thickness is 6". Please submit a foundation plan showing the minimum 6" foundation wall along the exterior of and the recessed footing for the proposed recessed shower for the new master bath.
|
6/2/2006
| GVB |
|
|
Please submit information for opening protection.
|
6/2/2006
| GVB |
|
|
Please indicate the existing electrical panel size and location and the proposed size and relocation.
|
6/2/2006
| GVB |
|
|
Please indicate the infiltration barrier on the typical wall section.
|
6/2/2006
| GVB |
|
|
Please indicate the proposed roof ridge sizes on the roof framing structural plan.
|
6/2/2006
| GVB |
|
|
The ceiling joist notes on the roof framing structural plan on sheet S-3 indicates the 2 x 10 ceiling joist max span as 17'. Several proposed ceiling joist loactions will be more than the allowed 17'. Please clarify.
|
6/2/2006
| GVB |
|
|
Please submit proposed door header details for the wall removal to install new exterior doors.
|
6/2/2006