All plans received after Oct 1, 2005 are required to be designed according to the 2004 Florida Building Code-Residential. Please resubmit plans referencing the 2004 FBC-Residential. Also specify the design criteria (on the plans) as per section 301.2.1.1. 2/10/2006 RCW
Please show a detail, on the plans, the overframing of the the roof. Specify the size and species of the wood members. 2/10/2006 RCW
Please provide a sectional view of the new porch beam resting on the existing block wall. 2/10/2006 RCW
Please specify if the structure is enclosed or partially enclosed. The truss package is designed to be enclosed. 2/10/2006 RCW
Please specify if the ceiling is to be sheathed and with what material. 2/10/2006 RCW
Specify the roof sheathing and nailing pattern. 2/10/2006 RCW
Please clarify what size and type of floor trusses or beams are to be used for the 26 foot span and the 17 foot span. (The small print details a truss and the large plan shows an LVL.) 2/10/2006 RCW